For SHE and ventilation
Special features
- VdS-certified
- For use in SHE- and SPS- systems
Technical data | |
Version | M9/...-500N/LA/EV1/.../VdS |
Electrical properties | |
Rated voltage | 24 V DC (-15 % /+25 %) |
Permissible ripple voltage | 2 Vss |
Nominal current | 1 A |
Cut-off | integrated, electronic load cut-off |
Protection class | III |
Mechanical properties | |
Stroke length approx. | 300 and 500 mm |
Pressure force | max. 500 N |
Tractive force | max. 500 N |
Locking force | 2000 N |
Running speed | ca. 8.3 mm/s |
Duty cycle | S3 ED 30 (2 min) |
Service life | > 10.000 cycles |
Dimension | (stroke + ca. 260 mm) x Ø 36 mm |
Electrical connection | |
Connection | 2 x 0.75 mm² |
Installation and ambient conditions | |
Ambient temperature | –5 °C up to +75 °C |
Protection category | IP 54 |
Authorisations and certifications | |
VdS-aknowledgement | G599007 according to VdS 2580 for use in SHE-systems |
Depending on the control panels used, increased currents in the starting torque must be taken into account when dimensioning the power supply and the cable cross-sections of the motor supply lines. Reliable operation is guaranteed when connected to appropriate control units from the same manufacturer. For operation on control systems from other manufacturers, conformity for functional safety must be requested.
With our free tool, you can find customized suggestions for the right drive for your requirements in the façade or on the roof in no time at all based on the window automation data you enter
Subject to technical changes; illustrations not binding.
voltage drive: | 24 V DC |
Application: | SHE & Ventilation |
Series: | M9 |
Approvals and certificates: | VdS |
- Do you have any questions concerning this product?
- Hier geht es zum www.Motorfinder.info
- LV-Heinze Texte
- Further products by Kingspan STG GmbH